Payal Power Systems (P) Ltd. :: Pure Sine Wave Inverters



Pure Sine Wave Inverters 5KVA-100KVA

 Su-Kam DSP Sine Wave Inverter Colossal series, with reliable, regulated and stabilized Pure Sine Wave Output, is a complete power generation system that is suitable for all types of commercial establishments and is capable of running everything from Lights Air Conditioners Lifts and Elevators & Welding Arch in the most cost effective manner.

Su-Kam DSP Sine Wave Inverter Colossal series supplies pure power is 100% safe to run most sophisticated, expensive and sensitive office equipment without the irritating humming sound. It has already established itself as a most reliable option to generators for Industrial application & work as a complete power generation selection.

Su-Kam DSP Sine Wave Inverter Colossal series produces pure sine wave- clean power. Digital Signal Processing (DSP), the world most advanced technology (meant for high-speed data processing), in conjunction with Sine Wave Technology delivers output which is completely stable and distortion free "Total Harmonic Distortion (THD) <3%". This power is actually purer than power supplied from the grid. This makes it absolutely safe to run even the most sensitive equipment. 

Su-Kam Sine Wave Inverter ensures
Full safety of highly sophisticated equipment
100% Pure, reliable and regulated power
Low running cost
Extended power backup time
Unbalanced load handling capability
It eliminates disturbing and irritating noise
Extended overload capability (upto 300%)
Start up without mains (Cold start)
Easy maintenance
Generator compatible

Monday, 24 September 2012

Payal Power Systems (P) Ltd. :: Commercial Vehicle Batteries Exide

We offer wide range of Commercial Vehicle Batteries Exide that is highly safe to use and gives long term service. Our range of Commercial Vehicle Batteries Exide has huge demand in the market for the excellent features like quality, performance and durability. These products are great in providing uninterrupted power supply to the vehicles they are used for. All our products meet international standards in quality and offered at an affordable price.

Commercial Vehicle Batteries Exide

Friday, 21 September 2012

Payal Power Systems (P) Ltd. :: Sinclair-I Series



SALIENT FEATURES
Sinclair-I Series 1 Phase in - 1 Phase out
 
  • Microcontroller based High Frequency design using IGBT
  • Active Power Factor Correction with input power factor > 0.98 for 10% to 100% load
  • Reduced hardware for increased reliability
  • High efficiency in both Mains and Battery Modes
  • Extra wide Input Voltage window range minimizing battery usage and enhancing battery utilization and life
  • Noiseless operation
  • SMPS Based Pure DC Charger with extended power, extended battery life and lower maintenance cost
  • Inbuilt static bypass
  • High crest factor, handles all high-inrush current loads without need for power rating upgrade
  • Multiple protection features to ensure load safety
  • DC-start function
  • User friendly LCD display
  • Heavy duty charger for long backup
  • Parallel redundancy is available in 6 and 10KVA
  • SNMP monitoring (optional)

Payal Power Systems (P) Ltd. :: Solar Systems

Solar Panels



Here are my top three tips on dealing with the question on whether or not you should take a look at installing a system to generate solar energy for your home. By using these tips, you can potentially save thousands of dollars in energy costs during the year. Just imagine how much happier you and your family would be, as well as realizing how the home generation and use of solar power helps the environment.

Friday, 14 September 2012

Payal Power Systems (P) Ltd. :: Gensets 125–200kVA


Technical Specifications
GENSET TECHNICAL DATA
GENSET PARAMETERS Units 
kVA rating/kW rating KVA125/100
Voltage  Volts415
Frequency Hz50
Current Amps174
Power Factor  0.8
ENGINE TECHNICAL DATA SHEET   
Engine model  S12-III
Rated Output kW114.7
No of Cylinders  6
Engine Configuration  Inline
Operating Cycle  4 Stroke
Displacement Lit7.12
Bore X Stroke mm105X137
Aspiration  TCA
Compression Ratio  16.8
Piston Speed m/s6.8
BMEP bar12.9
Firing Order  1-5-3-6-4-2
Flywheel housing SAESAE-2
Flywheel dimensions SAESAE-11.5
Starting System  Electrical
Rated Speed rpm1500
Overload capacity %10
Lube oil consumption % of fuel consumption lit/hr0.014
Lube oil change period hrs500
Alternator effeciency @ 75% load %powerol
DG set noise @ 1m  dB<75 dBA
Overall thermal effeciency of engine %42
Overall Dimension mm1727X932X1274.4
Engine Dry Weight kg598.6
Weight of radiator Kg47.5
Governor / Governor Class  A2
Fuel System   
Type  Rotary
Static Injection timing Degree BTDC20
Injectors holes Nos X size mm5X 0.21
Fuel Oil  High speed Diesel(HSD IS 1460:2005)
)
Fuel Filter type  Spin-on type with paper element
Filtration Capacity Micron5
Fuel transfer line restriction kPa30
Maximum lift of fuel transfer pump m1.87
Nozzle Injection Pressure bar290
Fuel Consumption  
50% Lit/Hr14.54
75% 20.38
100% 27.45
Lube Oil system   
Recommended Lube Oil  15W40 API CH4/ CI4
Lube Oil Pump  G-Rotor type
Lube Oil sump Capacity (max) Lit18
Lube Oil Sump Capacity (min) Lit15
Lube Oil system Capacity Lit19.8
Sump angle front up Deg15
Sump angle front down Deg15
Sump angle side to side Deg15
Lube oil pressure at rated loadkPa≥ 343.3
Lube Oil filter type  Full flow: Spin on cartridge type with Paper element
Filtration Capacity Microns15
Lube oil Flow rate LPM60
Lube oil change period Hrs500
Cooling System   
Type of cooling  Water Cooled
Engine coolant flow rate LPM140
Coolant pressure kPa68.64
Total quantity of coolant Lit25
Combustion air inlet flow m3/min8.9
Operating temperature of thermostatdegopening at 77-81,max open 94
Minimum coolant temperature alloweddeg-10
Maximum engine out coolant temperaturedeg105
Heat Rejection Details   
Heat Rejection to coolant kW59.73
Heat Rejection to Exhaust kW82.39
Heat Rejection to aftercooler (if applicable)kW12.1
Air Intake Details   
Intake air filter type  Dry type Air cleaner
Max allowable air restriction kPa6
Intake manifold pressure bar2.5 max
Maximum Intake manifold temperaturedeg55
Exhaust System   
Exhaust Silencer type  Residential type
Exhaust noise level at 1m dB<75
Max Permissible back pressure kPa9.99
Max Exhaust temperature deg600
Exhaust Gas flow  LPS0.155
Governor  Data   
Type  Mechanical
Whether adjustable droop provided  Yes
Transient speed increase for sudden decrease in load %As per IS10002
Transient speed decrease for sudden increase in load %
Recovery time sec
Valve Mechanism   
Type  4 valve/cylinder
Valve clearance cold, Intake/Exhaustmm0.4
Valve timing Inlet open/Inlet closedeg3 deg ATDC/23 deg APDC
Valve timing outlet open/outlet closedeg33 deg BBDC/1 deg ATDC
Other Information   
Max time to start engine from cold, attain rated speed & ready to take load sec6
Overload capacity  10%
 
Emission DetailsUnits 
ParametersCPCB normsActual
Nox (gm/kW-hr)9.27.54
CO (gm/kW-hr)3.50.49
HC (gm/kW-hr)1.30.18
PM (gm/kW-hr)0.30.076
Smoke (m-1)0.70.07
Average Sound level 1m from canopy≤ 75 dBA75
 
Overall Dimensions of GensetUnits 
Length mm3750
Width mm1300
Height mm2425
Height Including Silencer mm2425
Fuel Tank Capacity Lit250
Dry weight genset kg2359
Dry weight gensetkg2359

Note:

Above specifications are subject to change without notice due to continuous technical developments. All the above engine models conform to IS 10000 specifications. Engine governing as per BS 5514. Alternator: Reputed make conforming to respective IS standards.